AD 2005-17-04 Airworthiness Directives; McDonnell Douglas Model DC-10-10, DC-10-10F, DC-10-15, DC-10-30, DC-10-30F (KC-10A and KDC-10), DC-10-40, DC-10-40F, MD-10-10F, and MD-10-30F Airplanes; and Model MD-11 and MD-11F Airplanes

2005-09-26
2005-08-22
39-14225
FAA-2005-20662
Airframe
—

Models named: MD-11, MD-11F. Read the applicability below — it usually turns on serial or part numbers too.

Applicability*9

This AD applies to McDonnell Douglas Model DC-10-10, DC-10-10F, DC-10-15, DC-10-30, DC-10-30F (KC-10A and KDC-10), DC-10-40, DC-10-40F, MD-10-10F, and MD-10-30F airplanes as identified in Boeing Alert Service Bulletin DC10-26A065, Revision 1, dated May 20, 2005; and Model MD-11 and MD-11F airplanes as identified in Boeing Alert Service Bulletin MD11-26A060, Revision 1, dated May 10, 2005; certificated in any category.

Compliance

You are responsible for having the actions required by this AD performed within the compliance times specified, unless the actions have already been done. Inspection and Corrective and Other Specified Actions (f) Within 18 months after the effective date of this AD, perform a general visual inspection for damage to the Firex discharge pipes and wye assembly of the fire extinguishing system of the number 2 engine, and corrective and other specified actions; by doing all the actions specified in the Accomplishment Instructions of Boeing Alert Service Bulletin MD11-26A060, Revision 1, dated May 10, 2005 (for Model M-D11 and MD-11F airplanes); or Boeing Alert Service Bulletin DC10-26A065, Revision 1, dated May 20, 2005 (for Model DC-10-10, DC-10-10F, DC-10-15, DC-10-30, DC-10-30F (KC-10A and KDC-10), DC-10-40, DC-10-40F, MD-10-10F, and MD-10-30F airplanes); as applicable. Do the corrective and other specified actions, as applicable, prior to further flight. Note 1: For the purposes of this AD, a general visual inspection is: “A visual examination of an interior or exterior area, installation, or assembly to detect obvious damage, failure, or irregularity. This level of inspection is made from within touching distance unless otherwise specified. A mirror may be necessary to ensure visual access to all surfaces in the inspection area. This level of inspection is made under normally available lighting conditions such as daylight, hangar lighting, flashlight, or droplight and may require removal or opening of access panels or doors. Stands, ladders, or platforms may be required to gain proximity to the area being checked.” Actions Accomplished Previously (g) Actions accomplished before the effective date of this AD in accordance with the Accomplishment Instructions of Boeing Alert Service Bulletin MD11-26A060, dated July 20, 2004; or Boeing Alert Service Bulletin DC10-26A065, dated August 19, 2004; as applicable; are acceptable for compliance with the corresponding actions required by this AD. Alternative Methods of Compliance (AMOCs) (h) The Manager, Los Angeles Aircraft Certification Office, FAA, has the authority to approve AMOCs for this AD, if requested in accordance with the procedures found in 14 CFR 39.19. Material Incorporated by Reference (i) You must use Boeing Alert Service Bulletin DC10-26A065, Revision 1, dated May 20, 2005; or Boeing Alert Service Bulletin MD11-26A060, Revision 1, dated May 10, 2005; as applicable; to perform the actions that are required by this AD, unless the AD specifies otherwise. The Director of the Federal Register approved the incorporation by reference of these documents in accordance with 5 U.S.C. 552(a) and 1 CFR part 51. Contact Boeing Commercial Airplanes, Long Beach Division, 3855 Lakewood Boulevard, Long Beach, California 90846, Attention: Data and Service Management, Dept. C1-L5A (D800-0024), for copies of this service information. You may review copies at the Docket Management Facility, U.S. Department of Transportation, 400 Seventh Street SW., Room PL-401, Nassif Building, Washington, DC; on the Internet at http://dms.dot.gov ; or at the National Archives and Records Administration (NARA). For information on the availability of this material at the NARA, call (202) 741-6030, or go to http://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations.html. Issued in Renton, Washington, on August 10, 2005. Kalene C. Yanamura, Acting Manager, Transport Airplane Directorate, Aircraft Certification Service. [FR Doc. 05-16268 Filed 8-19-05; 8:45 am] BILLING CODE 4910-13-P

Unsafe condition

This AD was prompted by reports of freezing damage to the Firex discharge pipes and wye assembly of the number 2 engine, and one report of a level 1 ENG FIRE AGENT LO alert during flight. We are issuing this AD to prevent accumulation of water in the discharge pipes and possible consequent freezing damage to the discharge pipes and wye assembly, which could lead to failure of the fire extinguishing system during a fire in the number 2 engine.

Read the original on the Federal Register →

You just looked this one up by hand

TrackAD holds all 12,278 of them and matches them against the aircraft you actually look after — airframe, engine, propeller and appliances in one pass — then works out what falls due and when.

Look round a real shop first Start free

The demonstration shop is eleven real aircraft with a year of work behind them. No account needed.

The directive text above is reproduced from the Federal Register, a work of the United States government and in the public domain. The separation into applicability, compliance and required actions is TrackAD's.*1